Opto-Isolated Circuit Checks Three-Phase Power Presence and Sequence
- Brian Dipert
- 548 reads
Three opto-isolators and logic checks whether all three AC phases are present and whether phase B has the expected polarity at phase A’s zero crossing.



A three-phase monitor can check for both a missing AC phase and incorrect phase order without relying on a specialized three-phase transformer. Stephen Woodward’s circuit assigns an opto-isolator to each phase, then uses logic to assess phase presence and compare the phase relationship at a defined point in the cycle. That makes the design an alternative for projects where sourcing a compact star-connected transformer is difficult or costly.
Three phases, two checks
The circuit addresses two separate fault conditions. First, all three phase voltages must be present and energized. A lost phase, often called single phasing, can cause damaging motor overheating. Second, the phases must connect in the intended sequence. A sequence error can make a connected motor turn in reverse, potentially damaging the driven equipment.
These checks rely on different features of the three-phase waveform. When all three phase voltages are present, their summed positive voltage remains above zero. Correct sequence can be checked at the positive-going zero crossing of phase A: phase B should be positive at that instant. The circuit detects phase presence through its summed signals and tests sequence by sampling phase B at the phase A crossing.

Figure 1. A transformer-based three-phase detector provides the comparison point for the opto-isolated alternative.
Optical isolation replaces specialized magnetics
Woodward began with a practical sourcing problem: the star-connected three-phase transformer used in an earlier detector was not easy to find through familiar distributors, and available units could be expensive. Three individual single-phase transformers were another possibility, but they offered no clear advantage in cost and would take more space. The alternative uses one opto-isolator per AC phase, providing isolation while avoiding that transformer arrangement.
In the Figure 2 circuit, resistors R1, R2 and R3 each have a resistance of 1000 Vin,rms ohms and a power rating of Vin/1000 watts, as specified by the design. Each opto-isolator converts the presence and polarity of its AC input into a signal for the logic section. The design therefore separates phase sensing from the logic that evaluates whether the signals meet the two operating criteria.

Figure 2. One opto-isolator monitors each phase. The resistor values and power rating are given in terms of the input RMS voltage.
How the circuit identifies a missing phase
The phase-presence check uses signals at pins 3, 4 and 5 of U2. If one phase voltage is missing, at least one of those pins remains at a constant +5 V. U2 pin 6 then goes low periodically. That transition turns on Q4, which discharges C2 and holds U2 pin 2 low. In this condition, U2 pin 8 goes high; the signal is inverted at pin 10, producing a low status output to flag the fault.
This path responds to a phase-presence problem independently of the sequence test. That distinction matters in a monitor: a status indication should reflect whether the inputs satisfy both checks, since three signals can be present while their order is wrong.
Sampling phase order once per mains cycle
When all three phases are present, phase A provides the timing reference for the sequence check. Its signal reaches U1 pin 4, where a regenerative, or Schmitt, trigger cleans it into a clock signal at U1 pin 11. Once per AC mains cycle, that clock causes U1 pin 12 to capture the complement of phase B at the phase A positive-going zero crossing.
The expected result is a logic one. If the sampled value is zero, phase B did not have the required polarity at the reference crossing, so the sequence criterion has failed and U2 pin 10 goes low to indicate a not-OK status. A logic one means the sampled relationship satisfies the check.
The sampling interval follows the mains frequency: one cycle is 16.7 ms at 60 Hz or 20.0 ms at 50 Hz. The detector thus evaluates phase order at a consistent point in each cycle rather than relying on an unspecified comparison between the three waveforms.
What the alternative changes
The design’s practical contribution is its sensing approach. For engineers building a three-phase fault monitor, opto-isolators offer a way to avoid tracking down a particular three-phase transformer or fitting three separate transformers. The logic still checks the two conditions that matter to the application: phase continuity and the expected order. Component selection and the stated resistor sizing remain tied to the input RMS voltage.
Woodward’s circuit revisits an earlier magnetic detector with a simpler, non-magnetic arrangement. Its central idea is to make the waveform itself provide both checks: the combined phase signals expose a missing input, while a phase-A crossing provides the instant to test phase B’s polarity.